Reserve a pilot slot

Fold flat. Land anywhere. Live, farm or host guests by the next sunrise.

水M05 Systems · KUMO loom · with MIZU

Water from night air.
Sized for the residual.

Recycle every litre you can. Then pull only what is lost — and what you drink — out of the desert night: sorbent beds load in the dark, a sealed morning chamber gives the water back to a night-cooled condenser, and four barriers make it safe.

5–13 L / person / day harvested calculated 5–15× smaller than all-from-air calculated 24 kg sorbent per KUMO-12 rack 86 named parts in the model below EXPERIMENTAL
環01 Recycle first

Most of the water is never made. It comes back.

A desert harvester that makes all of a household’s water from air would be enormous. KUMO is sized only for the residual: the few per cent the MIZU water organ cannot return, plus what people drink and cook with.

Used each day
74 L recycled by MIZU
82.5 L
Harvested by KUMO
6 L lost2.5 L drunk
8.5 L
harvest = people × (demand × (1 − net recovery) + 2–3 L drinking & cooking) · shown: 80 L, 92.5 %, 2.5 L calculated
Demand target
60–100L/p/d

Water-conserving household.

Net recovery assumed
90–95%

In desert conditions; vendor states up to 97 % with rain make-up.

Residual calculated
5–13L/p/d

What the night air has to supply.

雲02 Anatomy · KUMO-12 installation

One rack, one day, nine moves.

A KUMO-12 rack on one jo tile, its glazed collector, the Miura condenser wing, the sump, the treatment train and a KRES-7 mast — every pipe drawn where it runs. Play the day, or pull it apart: explode the rack, cut it in half, click any part.

Fig. 02 · M05 KUMO-1201 · Size for the residual24 h · one cycle
Air · vapourHeatLiquid waterCold mass loopDC powerData

Drag to orbit · right-drag to pan · click a part · click, then scroll to zoom

This browser has no WebGL. The nine steps and the part index below describe the whole installation.
  1. 01Size for the residual 24 hThe configurator computes harvest = people x (demand x (1 - net recovery) + 2-3 L drinking and cooking), with demand 60-100 L/person/day (water-conserving) and 90-95% net recovery in desert conditions, giving about 5-13 L/person/day. Yield per kg is taken from single-cycle passive data, not lab multi-cycle data.
  2. 02Night capture 22:00–06:00Rack louvres open and low-power DC fans pull air through the sorbent beds - CaCl2-hydrogel composite or MOF-303 bonded to folded copper lamellae (v2 cassette). The rack runs one cycle per day; shaded daytime desert air (5-15% RH) is below the MOF-303 uptake step, so there is no daytime capture.
  3. 03Morning release 07:00–11:00The beds are shuttered into a sealed chamber and heated by a glazed solar-thermal collector loop; PV-T backsheet heat is used only as preheat or for CaCl2 composites. The governing check is p_sat(T_cond) / p_sat(T_bed) <= 0.1 for MOF-303 (e.g. condenser 25 C and bed about 70 C) or <= 0.2-0.25 for CaCl2 (bed about 55-60 C at a 25 C condenser). A DC trim heater fills cloudy-morning gaps.
  4. 04Condense 07:30–11:00Vapour goes to a condenser backed by night-cooled thermal mass or ground-coupled water that is separate from the potable tank, with a radiative-cooling coating on its shaded face; condensate drips into a weighed sump. Condenser temperature and the residual sorbent loading at the end of each release are logged.
  5. 05Verify 11:00Conductivity, turbidity and temperature are logged; water defaults to the grey loop until in specification.
  6. 06Purify 11:10Activated-carbon polish, then a calcite/dolomite mineral cartridge with CO2 dosing from a food-grade cylinder, then UV-C LED at 265-280 nm, then a chlorine residual for storage. Lithium checks apply only if a LiCl sorbent is used.
  7. 07Store 11:20Food-grade bladder in the base cells of the KRES mast (3-6 m gravity head) with a radiative-cooled top.
  8. 08Distribute any hourGravity to JO-PORT potable islands; DC booster pump; UV ring at each tap as the final barrier.
  9. 09Fallback alwaysFog-mesh skin on coastal deserts and ridges, a commercial hydropanel or AWG, or a truck fill port; the harvester never carries life safety alone.

Part index · 86 parts in ten subsystems

Click a name to find it in the model. Specs marked target are Anyground design targets; output numbers are calculated from single-cycle passive yields.

Rack & air path14

Sorbent cassettes12

Release chamber9

Solar-thermal loop11

Condenser & cold mass10

Sump & verification8

Purification train8

KRES mast storage6

Distribution5

Site & fallback3

吸03 Inside a cassette

A drawer of folded copper that breathes once a day.

Each of the twelve cassettes holds 2 kg of sorbent bonded to a folded copper lamella. The folds make long open channels for night air and put a heated tube under every fold for the morning.

Fig. 03 · Cassette slice · 380 mmNight · loading

Drag to orbit · click a layer

Folded copper lamella · sorbent coat · brazed heat tubes · supply and return manifolds · dust screens · handle · RTD · seals · passport tag.
Bed loading schematic
25%
Water in this cassette calculated
0.15L

2 kg × yield per kg per cycle, at the loading shown.

Bed temperature
ambient
p ratio in release
0.10

Set by the condenser and bed temperatures in section 04.

  1. Night. Louvres open, fans pull air along every channel; the coat loads and darkens. Shaded daytime air at 5–15 % RH sits below the MOF-303 uptake step, so there is no daytime capture.
  2. Morning. The rack is shuttered into a sealed chamber. Hot fluid from the glazed collector runs the tubes; vapour leaves for the condenser and the coat dries back.
理04 The governing check

Water leaves the bed only if the condenser is cold enough relative to it.

During release the bed “sees” the vapour pressure of the condenser. If psat(Tcond) / psat(Tbed) sits below the sorbent’s uptake step, the bed gives its water up. That is why release happens in the cool morning against a night-chilled mass — not at noon.

Sorbent
A · Saturation vapour pressureBuck equation · kPa
B · Uptake vs relative pressureschematic isotherm shape, normalised
Release pressure ratio calculated
—

psat(Tcond) / psat(Tbed) — e.g. 3.17 kPa / 31.2 kPa = 0.10 at 25 °C / 70 °C.

Limit for this sorbent
—

≤ 0.1 MOF-303 · ≤ 0.2–0.25 CaCl₂ composite.

Bed needed at this condenser calculated
—°C

A 35–42 °C midday condenser would need an 85–95 °C bed.

Working swing schematic
—%

Loaded at night minus left after release, as a share of the step.

Chart B is a shape, not a measured isotherm: MOF-303 is drawn with its sharp uptake step just above the 0.1 release ratio and above shaded daytime desert air; the CaCl₂ composite takes water up gradually. The 0.1 and 0.2–0.25 limits, the 2–4 kWhth/L and every yield come from the concept’s verified numbers.

量05 Size a site

How many racks, how much sun.

The configurator’s formula, live. Yields are single-cycle passive figures, not lab multi-cycle data — the same model drives the readouts in the 3D figure above.

Sorbent yield, one cycle per day

L per kg sorbent per day. MOF-801 Arizona and MOF-303 real-desert figures are measured; the CaCl₂-hydrogel range must be measured on the KUMO-2 bench.

Harvest needed

34L/day

8.5 L per person · 9.7× smaller than making all 330 L/day from air calculated

KUMO-12 racks5 vs 46 if all from air

7.2 L/day per rack = 24 kg × yield · each rack 0.91 × 1.82 m, one jo tile

Release heat calculated
91kWhth/day

2.7 kWhth/L = 0.8 kWh/L ÷ efficiency

Collector area calculated
52m²

13 m² per person · 31 jo tiles

Electric calculated
11kWh/day

Fans 7.2 + MIZU ≤ 9.6 (1 unit at rated 400 W)

KRES-7 buffer
59days

2,000 L ÷ daily harvest

Refrigeration AWG for comparison: about 0.3 kWh/L at 26.7 °C / 60 % RH — 10 kWh/day here — but it stops below 30–35 % RH, which is most desert nights. Collector yield uses the PV-T backsheet figure (7 kWh/m²/day × 0.2–0.3) as the concept does; the glazed collector’s real yield is a KUMO-2 measurement.

守06 From condensate to cup

Condensate is nearly pure. That is the problem — and the start.

Water from air carries no minerals and can carry dust or salt from the bed. It is weighed and logged, kept on the grey loop until in specification, then polished, remineralised, disinfected and stored with a residual. The tap adds a last UV barrier.

  1. 01Weighed sumpL per cycle → L/kg/day
  2. 02Sensor gateconductivity · turbidity · temperature; grey until in spec
  3. 03Activated carbonpolish
  4. 04Calcite / dolomite + CO₂food-grade; refill 6–12 months target
  5. 05UV-C LED265–280 nm · DC, a few watts
  6. 06Chlorine residualfor storage
  7. 07KRES-7 bladder~2,000 L · radiative-cooled top calculated
  8. 08JO-PORT → tap UV ringgravity + DC booster · final barrier
KUMO rack at midday with louvres closed, piped to PV-T panels; Miura condenser wing on the shaded side; mineral cartridge and UV ring on the tapI08 · Desert water rack
I08Midday: louvres closed for release, condenser wing on the shaded side, UV ring at the tap.Concept visual · AI

Fallback, always

The harvester never carries life safety alone.

  • Fog-mesh skin on coastal deserts and ridges
  • A commercial hydropanel or AWG for make-up
  • A truck fill port straight into the mast bladder
  • Lithium checks apply only if a LiCl sorbent is used
KUMO-12 folded
0.91 x 1.82 x 2.00 (1 jo) m
Deployed
1 jo + Miura condenser wing 3.64 x 1.82
Mass
280 kg target
Price band
$14,000-28,000 illustrative
KRES-7 mast
diameter 1.20 x 6.30 · stores about 2,000 L
証07 The numbers

Single-cycle, passive, in real deserts.

KUMO is sized on field yields from one cycle per day. The famous 1.3 L/kg/day figure needs rapid active cycling indoors — it is listed, and it is not used.

QuantityValueUnitBasisSource
MOF-801 passive single-cycle desert yield, Arizonaabout 0.1L/kg/daymeasureddoi.org · 10.1126/sciadv.aat3198
MOF-303 fully passive harvester, real desert climateabout 0.285L/kg/daymeasureddoi.org · 10.1016/j.device.2023.100054
CaCl2-hydrogel composite, single cycle per day0.3-0.8L/kg/daytargetmust be measured on the KUMO-2 bench
MOF-303 1.3 L/kg/day (indoor, 32% RH, 20-minute rapid cycling with active heating)active multi-cycle, not applicable to KUMOL/kg/daymeasureddoi.org · 10.1021/acscentsci.9b00745
Vapour-pressure check for desorption into a condenser<= 0.1 (MOF-303); <= 0.2-0.25 (CaCl2)p_sat(T_cond)/p_sat(T_bed)calculatede.g. p_sat(25 C) 3.17 kPa / p_sat(70 C) 31.2 kPa = 0.10; a 35-42 C midday condenser would need an 85-95 C bed
Heat needed per litre harvested2-4kWh_th/Lcalculated0.8 kWh/L desorption enthalpy / 20-40% system thermal efficiency
PV-T backsheet thermal yield at a 60 C outletabout 1.4-2.1kWh_th/m2/daycalculated7 kWh/m2/day x 0.2-0.3
Collector area per person for drinking and cooking water only (2-3 L)about 2-9m2calculated2-3 L x 2-4 kWh/L / 1.4-2.1 kWh/m2/day
WOTA Unit treatment capacity (not demand)438-720L/dayclaimedwota.co.jp
WOTA Unit recovery, with rainwater replenishmentup to 97%claimedwota.co.jp
Harvest need per personabout 5-13L/daycalculated60-100 L demand x 5-10% loss (3-10 L) + 2-3 L drinking and cooking
Harvester size reduction from recycle-firstabout 5-15xcalculated60-100 L/person/day / 5-13 L/person/day, central range
KUMO-12 rack output (24 kg sorbent, one cycle per day)2.4-12L/daycalculated24 kg x 0.1-0.5 L/kg/day; about 0.3-1.5 persons' residual per rack
Refrigeration AWG energy at 26.7 C / 60% RH; stops below 30-35% RHabout 0.3kWh/Lmeasureddoi.org · 10.1088/2634-4505/accec9
Annual PV yield loss of a PV-T panel vs a ventilated reference panel<= 3%targetAnyground gate
試08 Twelve months to prove it

KUMO-2: two beds, ninety logged nights.

EXPERIMENTAL (passive sorbents at pilot scale; WOTA Unit pre-mass-production; integration unbuilt). The recycle-first architecture with commercial make-up is the investable core.

Build

KUMO-2 bench: two beds, 2 x 2 kg sorbent (CaCl2-hydrogel first, MOF-303 if purchasable), glazed solar-thermal collector with a PV-T preheat panel, night-cooled condenser mass separate from storage, treatment train with CO2 dosing; at an arid field site plus a climate chamber.

BOM$15,000-35,000target

Test · 90 days

90 days of logged L/kg/day against night RH and temperature on one cycle per day; condenser temperature log; residual loading at end of each release; collector heat delivered per litre; PV yield vs a ventilated reference panel; full potable lab panel after treatment; salt carry-over checks.

Pass

>= 0.3 L/kg/day field mean at 20-40% night RH for CaCl2 composites, or >= 0.2 L/kg/day for MOF-303, on one cycle per day; measured heat <= 4 kWh_th/L; <= 3% annual PV yield loss vs a ventilated reference panel; potable lab pass.

Kill → fallback

< 0.15 L/kg/day or unsolved salt carry-over: buy commercial hydropanels or AWG/MOF units (SOURCE, AirJoule, Ahbstra class) for make-up and keep the recycle-first architecture.

Named risks

  • MOF availability and price unknown
  • Collector area per person larger than the roof allows at low-yield sites
  • Dust fouling of sorbent beds
  • Salt leaching from composites
  • Condenser mass too warm after hot nights